Two questions:

  1. Does vapour condense anywhere in the structure, and if so, how much.
  2. Can the structure dry out over the summer, or does the moisture accumulate year on year.

The second is the more important: a structure tolerates seasonal condensation if it dries out afterwards. What it does not tolerate is accumulation.

Because the structure is closed: moisture that gets between the sections cannot simply evaporate. In a thick brick wall moisture spreads out and dries; here it stays where it formed.

Add to that the fact that corrosion of steel needs exactly this — sustained moisture.

The basic rule: vapour permeability should increase outwards. The vapour control layer goes on the inside and the permeable layer outside.

The cold spot is where the vapour condenses. So good thermal bridge handling is also moisture protection. The steel thermal bridge.

How the building is used: how many people, how much cooking, whether there is mechanical ventilation.

Air flowing out through a gap carries far more moisture into the structure than diffusion does. Airtightness.

The simplified, steady-state procedure is sufficient for many cases. Where the build-up is unusual, the load is high or the structure is sensitive, a transient calculation is warranted, handling the seasonal cycle and the moisture storage of the materials.

  • If condensation occurs and does not dry out: change the build-up, do not accept it.
  • If it is borderline: the quality of the work decides — the continuity of the membrane and the airtightness are then critical.
  • If it passes comfortably: look at the connections separately anyway, because the surface calculation does not include them.

The moisture calculation is not bureaucracy but the only way to “see inside” the structure before it is built.